DC4500 Oringinal Factory Settings

Day Random
Hour Random
Minut Random
Temperature Fahrenheit
Conductivity Set point 2000 S
Delta Differential 100 S
Low Alarm 100 S
High Alarm 4000 S
Feed Mode Pulse Timer
Pulse Timer 10 seconds
Pulse Count 1 flow meter count
% Time – Cycle Time 10 Minutes
% Time – 10%
Feed after Bleed 10%
Feed after Bleed – Limit 10 Minutes
Limit (Feed & Bleed) 10 Minute Limit
Flow Alarm (On/Off) Off
Trip (Rise/Fall) Rise
4 mAmp setting 0 S
20 mAmp setting 20,000 S
Display (uS/PPM TDS) S
Pump Pulse Feed 100 strokes/minute
Pump Pulse Biocide #1 101 strokes/minute
Pump Pulse Biocide #2 102 strokes/minute
Controller Cooling Continuous/Timed Continuous
Biocide Lockout 0 Minutes
Biocide Prebleed 0 Minutes
Biocide Week Cycle 4 Weeks